- Electronic Fault Light -

Our DC (and AC/DC) compressors come with an LED fault light on the electronics module.  If the module detects an error, the light will blink from 1 to 5 times, repeating every 4 seconds.  Refer to the table below to determine the fault detected.  

 

Number of Flashes Error Type
5 Thermal Cut-Out of Electronic Unit

The electronic unit is too hot.  Either the air temperature is very high, or the refrigeration system is overloaded.

4 Minimum Motor Speed Error

The motor cannot maintain its minimum speed of 1,850 RPM.  The refrigeration system is probably overloaded.

3 Motor Start Error

The rotor is blocked or the differential pressure in the refrigeration system is too high (>5 bar).

2 Fan Over-Current Cut-Out

The condenser fan is drawing more than 1 amp peak from the electronic module.  It is probably defective.

1 Battery Protection Cut-Out

The DC voltage from the batteries is too low (less than 9.6V).  Either the batteries are drained down or there is a problem with the electrical supply.